Commercial Refrigeration 2019

HFCs R-134a and R-404A have been widely used in commercial refrigeration. Lower GWP non-flammable HFCs and HFC/HFO refrigerants are now being used or implemented, with R-134a continuing to be used for centralised systems in cascade circuits. Where mildly flammable A2L refrigerants can be used HFC/HFO blends with GWPs < 150 and HFOs are being adopted.

Commercial refrigeration covers a wide range of premises from small cafes to large supermarkets, and refrigeration requirements from frozen to chilled produce. The main categories are:

• Hermetically sealed equipment for display cases (for smaller retail premises)
• Condensing Units (for smaller retail premises)
• Centralised Systems (for larger supermarkets)

For larger supermarkets, energy use is typically considered as a whole, including the building HVAC, water use, lighting and the commercial refrigeration, with heat recovery being a key contributor to minimising energy consumption particularly where space heating is a seasonal requirement. For smaller stores heat rejection from display cases can contribute to additional air-conditioning load or provide useful heat in cooler climatic conditions.

refrigeration

F-Gas Regulation

In addition to the general F-Gas Regulation requirements and the HFC phase-down leading to the use of lower GWP refrigerants, the commercial refrigeration sector has two specific use bans in addition to the ban on the use of virgin refrigerants with a GWP higher than 2500 for the maintenance of existing installations from 1 January 2020.
• Stationary refrigeration equipment, that contains, or whose functioning relies upon, HFCs with GWP of 2 500 or more except equipment intended for application designed to cool products to temperatures below – 50 °C.

from 1 January 2020

• Multipack centralised refrigeration systems for commercial use with a rated capacity of 40 kW or more that contain, or whose functioning relies upon, fluorinated greenhouse gases with GWP of 150 or more, except in the primary refrigerant circuit of cascade systems where fluorinated greenhouse gases with a GWP of less than 1 500 may be used.
from 1 January 2022

Hermetically sealed equipment for display cases

These hermetic systems are typically used in convenience stores, mini-supermarkets and other similar retail premises. Regulation (EU) 2015/1095 establishes energy efficiency eco-design requirements for commercial refrigeration cabinets. Historically they have used R-134a and R-404A. Some units with small refrigerant charges that previously used R-134a are now using a small hydrocarbon refrigerant charge, similar to domestic refrigerators. However, where the use of highly flammable hydrocarbons is a concern, the HFOs R-1234yf and R-1234ze (E) are mildly flammable very low GWP (< 1, lower than hydrocarbons) alternatives to R-134a and achieve similar energy efficiency. For the replacement of R-404A, HFC/HFO blends offer similar performance for this application and are either non-flammable lower GWP refrigerants (R-448A, GWP 1387) or mildly flammable (A2L classification) with GWPs less than 150 (R-455A, GWP 148; R-454C, GWP 148) and offer similar or improved energy consumption compared to R-404A.

 

commercial-refrigeration

Condensing Units

A condensing as a minimum consists of a compressor, a condenser and a fan, and it is located outside or where there are several units potentially in a small machine room with ducted outside air and fan cooling. When connected to display units having evaporators it forms a refrigeration circuit. Typically, condensing units are used for premises with small cooling capacity requirements such as convenience stores, mini-supermarkets and restaurants. The condensing unit can have several compressors, are designed for several capacities and are standardised equipment. Since July 2018 new units must meet the energy efficiency Eco-Design requirements of Regulation (EU) 2015/1095. The most common refrigerants have been R-134a for medium temperatures (typically 0°C and 10°C) and R-404A for medium and / or low temperatures (<-18°C) for food storage.

Lower GWP non-flammable HFCs and HFC/HFO blends can be used to retrofit or replace R-134a or R-404A for current equipment taking into account the particular refrigerant performance, equipment manufacturer approval and for R-404A replacements, the discharge temperatures achievable with the replacement refrigerants. While R-134a has a GWP less than 2500 limit, lower GWP alternatives can be used and include R-450A (GWP 605) and R-513A (GWP 631). For R-404A replacement the options include R-407A, R-407F, R-407H, R-448A, R-449A, and R-452A having GWPs in the range 1387 to 2140.

The application of refrigerants with a GWP < 150 leads to the use of mildly flammable A2L fluorocarbon-based refrigerants or highly flammable hydrocarbon refrigerants, and requires the condensing unit design, location, and refrigerant charge to take into account the specific requirements for flammable refrigerants. For medium temperature applications the HFOs R-1234yf or R-1234ze(E) offer similar energy efficiency to R-134a. For R-404A, the possible A2L refrigerants include R-454C, R-455A and R-457A, all having GWPs below 150.

Centralised Systems for supermarkets

Large supermarkets have centralised systems as they usually achieve better energy efficiency than stand-alone display cases and condensing units and allow for effective heat recovery and systems to improve the energy consumption of the overall store. A machine room contains systems that operate at two temperature ranges, -10 and -15°C for the preservation of fresh products (medium temperatures) and the other at around -35 to -38°C for frozen products (low temperatures).

Until recently, centralized direct-expansion system using R-404A in low and medium-temperature refrigeration systems were dominant and while they offered many advantages in terms of performance, the long pipe runs, many joints and large refrigerant charges meant that installation and maintenance needed to be at an extremely high standard to minimise refrigerant leakage. The F-Gas Regulation use ban, requires from 1 January 2022, new large multipack centralised refrigeration systems to have refrigerants with a GWP < 150 except in for the primary circuit of a cascade system where refrigerants with GWP <1500 are allowed. The 1 January 2020 ban on the use of virgin refrigerants with a GWP higher than 2500 for the maintenance of existing installations will affect this sector.

For new installations fluorocarbon-based refrigerants have an important role to play and can be used in cascade and/or indirect systems. A cascade system connects the low-temperature circuit to the medium-temperature circuit using an evaporator-condenser. The refrigerants at the two levels of temperature can be either different or identical depending on the requirements. Indirect systems have a secondary circuit containing a heat transfer fluid typically used for the medium temperature level. A cascade system for the low temperature level can be combined with an indirect system for the medium temperature level resulting in the primary refrigerant charge being confined to the machine room and related areas. System configurations for Cascade + Indirect systems compatible with the 2022 use ban already being used are:

• R-134a as the primary refrigerant, CO2 for low temperature cascade circuit and an indirect heat transfer fluid for medium temperature providing an energy efficient option
• A non-flammable HFC/HFO blend replacement for R-134a having a lower GWP around 600 such as R-450A and R-513A.

In the longer term, where flammable refrigerants can be used in the machinery room, the HFOs R-1234ze(E) or R-1234yf might be suitable as alternatives to the R-134a in the primary circuit.
For existing R-404A centralised systems, the HFC phase-down and servicing ban from 2020 are resulting in retrofits to lower GWP non-flammable refrigerants having GWPs less than 2500. The drive to replace R-404A with refrigerants having GWPs less than 2500 started before the 2014 revisions of the F-Gas Regulation, with R-407A and R-407F being widely used. More recently refrigerants with GWPs around 1400 to 1500 are being used such as R-448A, R-449A, R-407H. Retrofit experience has shown reductions in energy consumption with these refrigerants.